NH-YJV-1KV-3*25+2*16耐火電纜
更新時(shí)間:2024-08-21
NH-YJV-1KV-3*25+2*16耐火電纜高長(zhǎng)期工作溫度:阻燃聚氯乙烯絕緣和護(hù)套70℃和105℃,,氟塑料絕緣和護(hù)套200℃和260℃,交聯(lián)聚乙烯絕緣90℃,低煙無(wú)鹵阻燃聚烯烴70℃,低煙無(wú)鹵阻燃交聯(lián)聚烯烴90℃和120溫度
- 上一個(gè):YJV22-18/30KV-3*120高壓鎧裝電纜
- 下一個(gè):DJYPVR-500V-7*2*1計(jì)算機(jī)電纜
NH-YJV-1KV-3*25+2*16耐火電纜適用范圍:
本產(chǎn)品適用于工頻額定電壓0.6/1kV及以下配電線路或工業(yè)裝置中有耐火要求的固定敷設(shè)場(chǎng)所使用。
The product is suitable for use in power distribution lines or fixed installations with rated power-frequency voltage up to and including 0.6/1kV.
NH-YJV-1KV-3*25+2*16耐火電纜使用特性:
1.工頻額定電壓U0/U:0.6/1kV。
Rated power-frequency voltage U0/U:0.6/1kV.
2·電纜導(dǎo)體的zui高允許長(zhǎng)期工作溫度(PVC/XLPE):70℃/90℃.
Max.permissible continuous operating temperature of conductor (PVC/XLPE): 70℃/90℃
3·短路時(shí)(zui長(zhǎng)持續(xù)時(shí)間不超過(guò)5s)電纜導(dǎo)體zui高允許溫度
PVC:導(dǎo)體截面≤300mm2-160℃
導(dǎo)體截面>300mm2-140℃
XLPE:250℃
Max.short-circuit temperature of the conductor shall not exceed(5s maxiumduration):
PVC:cross-section of conductor≤300mm2-160℃
cross-section of conductor>300mm2-140℃
XLPE:250℃
4.電纜敷設(shè)時(shí)環(huán)境溫度應(yīng)不低于0℃
The ambient temperature under installation should not below 0℃
5.電纜的彎曲半徑:多芯電纜不小于電纜外徑15倍,單芯電纜不小于電纜外徑20倍。
The bending radius of a single-core cable should not less than 20 times of the cable diameter.
The bending radius of multicore-cable should not less than 15 times of the cable diameter。
型號(hào)用途: